Source
Adapted from my own handwritten and hand-typed notes from Year 1 to Year 3 of my EEE degree
When the load (or source) is connected in , each phase sits between two lines, so the relations between line and phase quantities change.
Balanced Y-Delta System
A Y source feeds a balanced load. Each load phase sees a line voltage:
KCL at the load nodes gives the line currents:
Line and Phase Current Phasors

So for a connection:
- the line currents lag the corresponding phase currents by
- the line voltage equals the phase voltage,
Easier Route: Convert to Y
Replace the load by its Y equivalent, , and solve one phase as in the Balanced Wye-Wye Connection:
then get the phase currents from .
Delta-Delta and Delta-Y Systems
For a source, the source voltages are already line voltages, and so on:
- -: , then the line currents follow from KCL,
- -Y: KVL around loop aANBba with gives
- both can also be done by replacing the source with an equivalent Y source of
Worked Example
A balanced abc Y source with V feeds a load of per phase:
- A
- A
- A, A
- A, A